Product description:
The EL6632 PROFINET IRT controller terminal offers the complete RT (real-time) or IRT (isochronous real-time) functionality and a wide range of diagnostic options. All services in accordance with Conformance Class C are supported. Depending on the cycle time, up to five PROFINET IRT or up to 15 PROFINET RT devices can be operated at the EL6632 in a line topology.
The maximum distance between two devices is 100 m. Protocols such as LLDP or SNMP can be used for network diagnostics.
Technical data EL6632
- Technology: PROFINET IO
- Number of ports/channels: 2
- Ethernet interface: 100BASE-TX Ethernet with 2 x RJ 45
- Fieldbus: PROFINET IRT controller
- Cable length: up to 100 m twisted pair
- Hardware diagnosis: status LEDs
- Power supply: via the E-bus
- Electrical isolation: 500 V (E-bus/Ethernet)
- Max. number of IRT-capable devices: 5 (depending on the cycle time and number of data)
- Max. number of RT-capable devices: 15 (depending on the cycle time and number of data)
- Minimum IRT cycle: 500 µs
- Minimum RT cycle: 1 ms
- Conformance class: C
- Protocol: RT or IRT
- Driver: TwinCAT 2.11
- Configuration: via EtherCAT master
- Current consumption E-bus: typ. 400 mA
- Special features: Conformance Class B, max. 5 IRT devices, max. 15 RT devices, min. 500 µs IRT cycle, min. 1 ms RT cycle
- Weight: approx. 75 g
- Operating/storage temperature: 0…+55 °C/-25…+85 °C
- Relative humidity: 95 %, no condensation
- Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27/29
- EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
- Protect. class/installation pos.: IP 20/see documentation